Home | Energy Physics | Nuclear Power | Electricity | Climate Change | Lighting Control | Contacts | Links |
---|
INTRODUCTION:
A nuclear reactor produces heat. That heat is used to produce high pressure (10 MPa) steam. The steam is expanded through a turbine connected to a synchronous electricity generator to produce electricity.
This web page describes the sodium-potassium alloy (NaK) loops that transport heat from the FNR liquid sodium pool to the steam generators at controlled rates.
In the described power system the sodium pool temperature is held nearly constant at about 460 degrees C by the physical properties of the FNR. The steam generator water temperature is held nearly constant at about 320 degrees C by the steam genertor's discharge pressure regulator setting. The NaK loop transports heat from the FNR sodium pool to the steam generator.The NaK loop temperature differenceis typically 120 degrees C at heavy loads and 138 degrees C at light loads. Changing the NaK circulation rate changes the rate of heat transport from the sodium pool to the steam generator and hence changes the rate of steam production. An advantage of this system design is that solid material temperatures remain nearly constant over the power modulation range, which minimizes thermal stress.
In a liquid sodium cooled FNR power plant, due to the chemical incompatibility between sodium and water and due to the radio activity of the sodium, the sodium in the sodium pool is double isolated from the steam generator water/steam. Heat moves from the atmospheric pressure liquid sodium (0.101 MPa absolute at the sodium pool surface) to slightly lower absolute pressure NaK by thermal conduction through the walls of the intermediate heat exchange tubes. A combination of natural convection and induction pumping causes liquid NaK to circulate through the intermediate heat exchange tubes, through the NaK pipe loops and through the steam generators. NaK is used because it remains a chemically stable low pressure high thermal and electrical conductivity liquid from room temperature up to over 500 degrees C.
The NaK is a fire risk if it is exposed to either water or the atmosphere. In order to quickly extinguish NaK fires each NaK loop is fitted with a dedicated Nak dump tank. When the argon pressure over the dump tank is removed the NaK loop gravity drains into its dump tank.
DUMP TANKS:
At the low points in the heat transport pipe loops are dump tanks with sufficient volume to accommodate all the NaK in that heat transport loop. Note that the NaK dump tanks must be rated as pressure vessels and must be fitted with high pressure argon relief valves vented to the atmosphere. Note that changing the temperature of the argon in the dump tank affects the argon pressure and hence the NaK column height. Hence each NaK loop needs its own argon pressure control and NaK level sensor for liquid NaK level regulation.
The NaK level control relies on argon pressure control by external low temperature argon valves. To charge the NaK loop argon is first injected into the top of the dump tanks while the displaced argon in the cushion tank is vented to the primary sodium pool space.
This arrangement requires reliable valves on small argon pipes connected to the dump tank that either vent the dump tank to the argon atmosphere or connect pressurized argon to drive NaK out of the NaK dump tank. Note that over time NaK vapor may tend to condense in the cooler vent line. This issue may require ongoing maintenance.
NaK LOOPS:
Each heat exchange gallery has an internal width of 8.0 m. Each heat transfer loop has one steam generator. There are 6 such steam generators per heat exchange gallery. The heat transfer loops are spaced at 1.5 m center to center and have 1.25 m off each side. Hence the overall gallery length occupied by equipment is:
5 (1.5 m) + 2 (1.25 m) = 10.0 m.
At the end of the Heat Exchange Gallery furthest from the airlock is the door to the stairwell.
Intermediate heat exchange bundles are immersed in the upper perimeter of the sodium pool. The 16 inch OD Pipes connecting the steam generators to the intermediate heat exchange bundles go straight through the sodium pool enclosure wall. Each pipe carrying hot NaK from an intermediate heat exchange bundle goes directly to its companion steam generator top manifold inlet port. Each pipe carrying cooler NaK back from a steam generator to its companion intermediate heat exchange bundle is routed through a flow meter (F) and then a vertical induction pump which in normal operation sets the NaK circulation rate and hence the thermal power conveyed by the heat transport circuit. Note that in normal full power operation this NaK circulation rate results in a NaK return temperature of about 330 degrees C.
There is a NaK drain to 1.7 MPa pressure rated NaK dump tanks located at a low point on the NaK return pipe between the steam generator and the induction pump. This drain pipe is connected so as to fully drain the NaK in the induction pump.
The lower steam generator manifold covers have a small drain plugs to allow drainage of trapped NaK from that manifold when service access inside that manifold is required.
In the event of a steam generator tube rupture the higher pressure water (~ 10 MPa) will enter the NaK loop where it will flash to steam and will rapidly chemically react producing hydrogen. These gases will blow the rupture disks on top of the large diameter NaK loop vents and will discharge H2 and steam out these vents.
Loss of NaK out this vent could potentially start a fire when exposed to air or water.
The steam pressure in the steam generator shell must be set sufficiently high to keep the steam generator water temperature and hence the NaK return temperature at 320 C, above the NaOH melting point. The NaK supply upper temperature is limited by the Na pool temperature. The NaK return temperature should be kept at about 320 degrees C to prevent NaOH depositing on heat exchange surfaces. The steam bypass valve from the steam generator to the turbine condenser is openned. Then evaportion of steam generator water will extract heat from the NaK and hence the sodium pool. The steam generator water level control system will automatically add replacement water as the cooling water evaporates.
In the event of a steam generator tube failure the intermediate heat transport fluid (NaK) must behave in a predictable manner to allow safe NaK loop shutdown. However, the NaK loop is presure rated for 1.7 MPa working pressure at 800 degrees K (527 C) to allow safe relief of sudden unplanned steam generator tube failures.
The intermediate heat exchange bundles isolate the radioactive liquid sodium from the non-radioactive NaK. A vacuum is applied over the NaK which causes the NaK to operate at a lower pressure than the adjacent Na. Thus, subject to intermediate heat exchange bundle integrity, the heat exchange galleries should be radiation free. In the event of a leak in the NaK loop then Na, Ar or air flows into the NaK loop instead of NaK flowing out the NaK loop. Any radioactivity in the NaK indicates an intermediate heat exchange tube bundle leak. The vacuum supported NaK columns are high enough to ensure good NaK circulation.
If steam generator water leaks into the NaK circuit large volumes of hydrogen will instantly be produced. This hydrogen will be vented via two 16 inch OD vent pipes that terminate in rupture disks. An above normal pressure in the NaK indicates a steam generator tube leak.
If a tube leak is suspected the NaK in the heat exchange gallery and in the sodium pool space above the pool deck should automatically immediately drain down to its respective dump tanks.
Note that with a vacuum over the NaK,the argon gas pressure over the NaK dump tanks sets the top of NaK level.
Both ends of the steam generator NaK loop are potentially vented to the atmosphere via tall large diameter (16 inch OD) vents with ball checks and rupture disks.
In the event of a steam generator tube leak hydrogen gas will immediately form in the NaK loop and together with steam will violently expel some NaK up the large diameter vents. A top of vent vacuum space and a ball check and rupture disk are used to minimize discharge of NaK to the atmosphere.
REACTOR POWER
The reactor power is controlled by controlling the rate of heat extraction which is set by the speed of the NaK induction pumps. The liquid sodium temperature and steam generator water temperature remain nearly constant. This arrangement minimizes thermal stress through the heat transport system with time varying reactor power and protects the induction pump from exposure to high NaK temperature.
HEAT EXTRACTION
The steam bypass valve from the steam generator to the turbine condenser is openned. Then evaportion of steam generator water will extract heat from the NaK and hence the sodium pool. The steam generator water level control system will automatically add replacement water as the cooling water evaporates.
NaK PIPING
Except for parts directly exposed to the neutron flux that are made of HT-9,the NaK piping is executed with 316L stainless steel. The steam generator fuel tubes may be made of Inconel which closely matches the TCE of 316L SS. The issue is that unlike the sodium pool, the NaK can tolerate dissolved nickel. The NaK should contain enough Fe, Ni and Cr to be in equilibrium to minimize long term corrosion of 316L stainles steel. The sodium in the reactor pool contains free neutrons whiich can interact with dissolved nickel causing problems whereas the NaK contains no neutrons. The advantage of Ni is that it strengthens steels at high temperatures.
The NaK dump tanks are charged with sufficient NaK to fill the NaK circulating loop. Then compressed argon is added over the dump tanks to set the NaK level.
The NaK loop piping has 16.0 inch OD with 0.375 inch wall. The NaK loop is rated for a maximum working pressure of 1.7 MPa. The NaK referred to herein is a low temperature melting point alloy consisting of 77% K by weight. A major feature of this NaK is that it is liquid from below room temperature up to over 700 degrees C. This feature enables sodium melting by transfer of heat backward from the steam generators through the NaK to the sodium pool. NaK is not used in the sodium pool due to its inferior neutronic properties as compared to pure sodium.
The intermediate heat exchanger is counter flow and is realized with a single pass vertical tube bundle.
The intermediate heat exchange bundle top manifold connects to the steam generator top manifold via 16 inch OD schedule 40S stainless steel pipe. The intermediate heat exchange bundle bottom manifold connects to the steam generator tube side bottom manifold via a 16 inch OD schedule 40S stainless steel pipe. This pipe contains an induction pump that circulates NaK from the bottom manifold of the steam generator to the bottom manifold of the intermediate heat exchange bundle. This configuration provides heat exchange counterflow and permits removal and replacement of individual steam generators and induction pumps via overhead crane lifts. There is a gravity drain from the NaK loop to dedicated parallel connected NaK dump tanks. Three vertical vent pipes and a shared vacuum chamber are required for each NaK loop to trap and expel gases and to indicate the NaK levels.
The NaK pipes are supported by steam generator and the induction pump at the heat exchange gallery end and are supported by a steel frame fastened to the pool deck near the edge of the sodium pool. The hot wall and the pipe feed through fittings at the cool wall and the structural wall provide negligible pipe support.
HOT WALL NaK PIPE PASSAGE
The stainless steel surface of the hot wall is welded dirctly to the NaK pipes via an external metal pipe ring. The space between the hot wall and the cool wall above the pool deck is filled with ceramic fiber thermal insultion. The NaK pipes pass through clearance holes in the cool wall and the structural wall. Each these clearance holes is fitted with a seal doughnut ring seal to prevent argon passage. This arrangement provides for both translational and axial pipe movement caused by thermal expansion/contraction.
NaK pipe axial travel at the hot wall, assuming that the position of steam generator central axis is fixed is:
[36 inch) + (36 inch) + (48 inch) + 3 (40 inch)] X (16 X 10^-6 / deg C) X (500 -20) deg C
= 240 inch X 16 X 10^-6 X 480
= 1.84 inch
Thus the doughnut seals must provide for 16 inch OD pipe with up top 2 inches of axial parallel pipe travel,up to two inches of axial perpendicular pipe travel and that can fit within a 32 inch diameter circle.
HIGH TEMPERATURE GAS SEAL MATERIALS:
GraFoil- high temperature graphite based seal material.
Thermiculite-high temperture composite seal material
DOUGHNUT SEALS:
The NaK pipes pass through the cool wall and the structural wall via doughnut ceramic particle seals. These seals are effective at preventing low differential pressure argon leakage in the presence of changing pipe surface temperature, pipe radius, pipe axial motion and pipe lateral motion due to thermal expansion/contraction. However, it is essential to design the pipe support to minimize temperature driven vertical movement of the pipe axis with respect to the seal axis. For example, when the system is cooled from 460 degrees C to 120 degrees C for service the change in elevation of the pool deck is driven by a changing temperature SS height of 17 m whereas the change in elevation of the NaK hot pipe at the steam generator is driven by a changing temperature SS height of 7 m, so NaK pipe axis vertical movement at both the structural wall and the cool wall is a potential problem.
CERAMIC DOUGHNUT RING SEAL DESIGN:
Ceramic doughnut ring seals are intended for preventing low differential pressure argon leakage at points where NaK pipes pass through the cool wall and for preventing air leakage through the structural wall. The seal material is mixture of controlled size ceramic particles. The larger particles are too big to escape from the seal. The smaller particles provide the actual Ar seal and are kept in ce by the larger particle. The ceramic particles are retained by two rigid ceramic washers. The washer's ID is a sliding fit over the 16 inch OD 316L SS pipe.
At room temperature the ceramic particle doughnut inside diameter is a snug fit over the outside diameter of the 16 inch pipe. At room temperature the ceramic prticle doughnut OD is a loose fit to the ID of a ring of 30 inch OD thick wall steel pipe. The length of this thick wall pipe ring is about 6 inches.. The seal has two SS flat plate components. One SS plate has a 30 inch OD, the same outside diameter as the OD of the thick wall pipe. Both stainless steel flat plates have 22 inch diameter central holes. The remaining SS flat plate outside diameter is 32 inches and is chosen for easy welding to the cool wall or attachment to the structural wall.
Seal final assembly is via threaded hardware.
The ceramic particles should not be added until other seal and pipe installation steps are complete.
As the NaK pipe gets hot its OD increases which deforms the seal particle packing. The pipe can still axially slide through the seal in reponse to thermal expansion/contraction.
In principle a comparable giant ring seal can be used between the hot wall and the cool wall, close to the pool deck level. Radial thermal expansion of the sodium pool should drive a wedge under the cool wall seal support assembly so as to cancel out NaK pipe axis vertical movement with respect to the seal axis.
MELTING POINTS
NaK melting point = < 15 degrees C
This keeps the NaK liquid over its normal operting temperature range.
NaOH melting point = 318 degrees C
This keeps NaOH liquid during normal reactor operation but permits NaOH removal by cooling and filtering.
KOH melting point = 406 degrees C.
This keeps KOH liquid on the hot side of the NaK loop but permits continuous removal via a shunt filter across the induction pump.
Na2O melting point =
K2O melting point =
DENSITIES:
Na = 971 kg / m^3
K = 856 kg / m^3
Reference Wikipedia Sodium-Potasium alloy.
NaK containing 40% to 90% K by mass is liquid at room temperature.
NaK-77 eutectic contains 23% Na and 77% K by mass and is liquid over the temperature range -12.5 C to + 785 degrees C.
DENSITY OF NaK-77:
866 kg / m^3 at 20 degrees C
855 kg / m^3 at 100 degrees C
749 kg / m^3 at 550 degrees C
By interpolation density at 450 degees C is:
855 kg /m^3 - (350 / 450)(855 - 749) kg / m^3
= 855 Kg / m^3 - 82.44 kg / m^3
= 772.55 kg / m^3
The NaK eutectic column height H certain to be supported by one atmosphere is given by:
Rho g H = 101,000 Pa
or
H = 101,000 Pa/ [866 kg / m^3 X 9.8 m / s^2]
= 11.90 m
Hence the maximum NaK height at no NaK flow is 11.9 m above the bottom of the lower steam generator manifold.
At full flow the maximum NaK height above the liquid sodium pool surface is 11.9 m.
Hence the NaK column height available to accommodate flow induced pressure drops through the NaK loop is the difference in elevation between the sodium pool surface and the bottom of the lower steam generator manifold which is:
7.5 m - 2.5 m = 5 m
Expressed in pressure that is:
(5 m / 11.9 m) X 101,000 Pa = 42,437 Pa
We need to compare this driving differential pressure to the sum of the differential NaK flow induced pressure drops across the intermediate heat exchange bundle, the steam generator, the induction pump and the NaK loop piping.
HEAT CAPACITY OF NaK:
= 982 J / (kg-deg C)
NaK FLOW RATE:
At full power each NaK loop transports 20.8 MWt = 20.8 X 10^6 W = 20.8 X 10^6 J / s
Assume that at full power the NaK loop temperature drop falls to 100 deg C.
(20.8 X 10^6 J / s) /[(982 J / kg-deg C)X 100 deg C] = 211.81 kg / s
(211.81 kg/ s) / 772.55 kg / m^3 = 0.274 m^3 / s
THEORETICAL REQUIRED FULL FLOW PUMPING POWER:
Assume that the NaK loop flow induced pressure drop is as much as:
42,437 Pa.
The theoretical minimum power required tochieve this NaK circulation is:
42,437 Pa X 0.274 m^3 / s = 11,628 (kg / m-s^2) (m^3 / s)
= 11,628 kg m^2 /s^3
= 11,628 W
= 11.628 kW
If the induction pump is only 20% efficient this pump load would be:
5 X 11.628 kW = 58.14 kW
THEORETICAL FLOW INDUCED PRESSURE DROPS:
(differential pressure) X (area) X (velocity) = (mass flow rate) X (velocity)^2 / 2
(mass flow rate) = (volumetric flow rate) X (density) = (velocity) X (area) X (density)
Hence:
(differential pressure) X (area) X (velocity) = (velocity) X (area) X (density) X (velocity)^2 / 2
or
(differential pressure) = (density) X (velocity)^2 / 2
= [(density) / 2] X [(volumetric flow rate) / (area)]^2
(density) = 866 kg / m^3
(volumetric flow rate) = 0.274 m^3 / s
Thus:
(differential pressure) = (density) X (velocity)^2 / 2
= [(density) / 2] X [(volumetric flow rate) / (area)]^2
= [(866 kg / 2 m^3) X (0.274 m^3 /s)^2 / (area)^2
= (32.508 kg m^3 / s^2) / (area)^2
From FNR Induction Pump the open annulus cross sectional area of the induction pump is:
Pi (9 inch - 0.375 inch)^2 - (7.0 inch)^2]
79.767 inch^2
= 0.05146 m^2
Induction pump differential pressure drop:
32.508 kg m^3 / s^2) / (throat area)^2
= 32.508 kg m^3 / s^2) / (0.05146 m^2)^2
= 12,276 Pa
Steam Generator differential pressure drop:
32.508 kg m^3 / s^2) / (tube open area)^2
= 32.508 kg m^3 / s^2) / (198.91 inch^2)^2
= 32.508 kg m^3 / s^2) / [(198.91 inch^2 X (.0254 m / inch)^2]^2
=32.508 kg m^3 / s^2) / [(0.1283 m^2)]^2
= 1974.86 Pa
Intermediate heat exchange bundle differential pressure drop:
32.508 kg m^3 / s^2) / (tube open area)^2
= 32.508 kg m^3 / s^2) / (241.65 inch^2)^2
= 32.508 kg m^3 / s^2) / [241.65 inch^2 X (0.0254 m / inch)2]^2
= 32.508 kg m^3 / s^2) / [0.1559 m^2)]^2
= 1337.5 Pa
For a straight piece of 16 inch OD pipe connecting two elbows or manifolds:
(area) = Pi (8 inch - 3 / 8 inch)^2 X (0.0254 m / inch)^2
= 0.1174 m^2
Hence straight pipe differential pressure is:
32.508 kg m^3 / s^2) / (tube open area)^2
= 32.508 kg m^3 / s^2) / (0.1174 m^2)^2
= 2358.6 Pa
This pressure drop, even if repeated 6X due to elbows and manifolds, is still results in a total NaK flow induced loop pressure drop much less than the maximum available 42,437 Pa.
PRESSURES:
The NaK is kept in place by argon pressure over the NaK dump tank and the top vacuum. Opening a valve between the top of the NaK dump tank and the top of the NaK loop allows most of the liquid NaK to flow by gravity into the NaK dump tank. This is the primary means of NaK fire suppression.
Na, K PROPERTIES:
Na density = 0.971 g / cm^3
Na BP = 880 C
K density = 0.856 g / cm^3
K BP = 760 deg C
Note that the vapor pressure of K is higher than the vapor pressure of Na, which will limit the possible minimum vapor pressure at 500 degrees C.
SPECIFIC GRAVITY:
If there is a steam generator tube failure high pressure liquid water leaks from the steam generator into the NaK loop, the water instantly flashes to steam, hydrogen gas is generated and two gases bubble up therough the NaK. A rapid chemical reaction between the Nak and steam produces H2, KOH and NaOH. The KOH and NaOH may be either liquid or solid, depending on the temperature, but are more dense than NaK and hence sink to the bottom. The steam and hydrogen gas mix raising the pressure and blow out via a vent top rupture disk. The rapidly rising pressure closes the top ball check to the vacuum pump that otherwise evacuates argon, potassium vapor and sodium vapor to a cold trap for material recovery.
INDUCTION PUMP SUCTION HEAD REQUIREMENT:
From FNR Induction Pump the open annulus cross sectional area of the inductioon pump is:
Pi (9 inch - 0.375 inch)^2 - (7.0 inch)^2]
79.767 inch^2
= 0.05146 m^2
The axial flow velocity through this annulus is:
(0.274 m^3 / s) / 0.05146 m^2 = 5.324 m / s
differential pressure) X (area) X (velocity) = mass flow rate X (velocity)^2 / 2
(mass flow rate) = (volumetric flow rate) X (density) = (velocity) X (area) X density
Hence:
(differential pressure) X (area) X (velocity) = (velocity) X (area) X density X (velocity)^2 / 2
or
(differential pressure) = density X (velocity)^2 / 2
= 866 kg / m^3 X (5.324 m / s)^2 / 2
= 12,276 Pa
= .012276 MPa
Thus the induction pump inlet suction head requirement is easily met.
NATURAL CIRCULATION REQUIREMENT:
There must be enough natural circulation of NaK to remove fission product decay heat. This decay heat is quantified in the paper: Decay Heat In Fast Reactors.
&nnbsp;
NaK NATURAL CIRCULATION:
In normal full load reactor operation the reactor produces 1000 MWt of heat. When the chain reaction is off the reactor may still produce as much as:
0.08 X 1000 MWt = 80 MWt
of fission product decay heat.
After a few ____hours this fission product decay heat output diminishes to about 10 MWt
Hence ideally natural circulation of the NaK should run at over 8% of the maximum pumped circulation rate. Later natural circulation should contnue at 1% of the maximum pumped circulation rate.
The natural circulation rate is primarily limited by the temperature differences between the NaK rising legs and the NaK falling legs and by the viscous flow pressure drops across the intermediate heat exchange bundle and the steam enerator. Thus these pressure drops need to be quantified. An importnat issue is the NaK temperature in the falling leg feeding the intermediate heat exchange bundle. This leg needs to be well insulaed to promote natural circulation. There is a fundamental problem that to support a NaK pressure less than ambient in the sodium pool space the top of the steam generator needs to be not far above the pool deck. That is not a favorable position from a natural NaK circulation perspective.
However, a desirable feature of a low positioned steam generator is that in an emergency part or all of it can readily be flooded with water by gravity so as to achieve removal of fission product decay heat without requiring electrical power. This is a very important safety issue.
NaK THERMAL SIPHON:
Assume emergency cooling conditions when Na temperature = 450 degrees C and steam generator temperature = 100 degrees C. There is loss of house power and hence induction pumping has stopped.
The differential pressure established by the different temperature NaK columns under emergency cooling conditions is:
P = [(855 - 772) / 2] kg / m^3 x 10 m x 9.8 m / s^2
= 4067 kg m / s^2-m^2
Note the divide by 2 due to only partial heating and cooling in the intermediate heat exchange bundle and in the steam generator under emergency thermal siphon conditions.
Neglecting viscosity:
P = Rho V^2 / 2
or
Pb / Pa = (Vb/Va)^2
or
(Vb / Va) = (Pb / Pa)^0.5
Let Va correspond to normal full flow.
Let Vb correspond to thermal siphon flow.
Then:
(Vb / Va) = (4067 Pa / 54,713 Pa)^0.5
= 0.2726
Hence the emergency thermal siphon NaK flow is at least 27% of full NaK flow which is more than sufficient for removal of fission product decay heat.
Hence, provided that the fission power is zero a thermal siphon can be used to dump FNR supplied fission product decay heat. However, forced circulation NaK must be used if fission reactions continue. If the reactor overheats the fission power should drop to zero reducing the thermal output to just fission product decay heat.
PIPE FITTING DIMENSIONS
NaK Pipe: 16 inch OD = 0.4 m OD
NaK pipe flanges: 32 inch OD = 0.8 m OD
NaK pipe 90 degree elbows: inside radius = 16 inch = 0.4 m, outside radius = 32 inch = 0.8 m
NaK pipe 90 degree elbow projection = 32 inch = 0.8 m for pipe, 40 inch = 1 m for flange
NaK pipe 90 degree elbow centerline deviation = 24 inch = 0.6 m
NaK 16 inch X 16 inch X 16 inch pipe tee = 48 inch long
NaK 16 inch X 16 inch X 4 inch pipe tee = 36 inches long
NaK 16 inch X 4 inch X 16 inch elbow tee = 24 inches centerline deviation
PIPE MECHANICAL JOINTS:
A major constraint on assembly and service of liquid sodium cooled FNRs
is the flanged pipe joints necesssary for repeatedly connecting and disconnecting NaK transport pipes in the field. The assumed solution is precisely machined conflat flanges with chromium or nickel plated copper gaskets. The purpose of the chromium or nickel plating is to prevent the copper dissolving in hot Na and K. As compared to a high vacuum system, minor inward external fluid leakage is acceptable. The vacuum possible is limited by the vapor pressures of Na and K at 500 degrees C.
Copper melting point = 1084.6 degrees C
Chromium melting point = 1906 degrees C
Chromium can be electroplated onto copper.
Nickel melting point = ____ degrees C
Nickel can be electroplted onto copper.
FLANGED JOINT LEAK PREVENTION:
Bolted flange pipe joints are required in the argon filled space over the sodium pool space to enable practical replacement of intermediate heat exchange bundles. The aim of this design is to do all necessary to ensure that everywhere the NaK absolute internal pressure is lower than the surrounding absolute external fluid pressure. Hence if there is any NaK loop leakage in the sodium pool space it is argon or sodium leaking into the NaK, not vice versa. Some of the flanged joints in pipe containing NiK can be perimeter welded for seal certainty.
Above the liquid sodium surface in the sodium pool space the absolute external pressure is set by argon at 0.101 MPa.
Provided that the NaK absolute pressure at the sodium pool surface is less than 0.101 MPa, then below the sodium pool surface the absolute Na pressure will always be greater than the NaK absolute pressure. This effect occurs because the density of liquid Na is greater than the density of liquid NaK.
When air or argon at 101,000 Pa is the surrounding fluid the maximum NaK column height to a vacuum is:
h = 101,000 Pa / [(866 kg / m^3) X (9.8 m / s^2)]
= 11.9 m
Of this height at no NaK flow about 4 m are actually used. The induction pump induced NaK flow tends to increase the absolute pressure in the NaK feeding the intermediate heat exchange bundle inlet manifold. However, we have about a 7 m NaK head margin to compensate for the flow induced pressure drops.
HEIGHT ISSUES
The horizontal hot pipe axis is 2.5 m above the liquid sodium pool surface, Hence the top of the NaK is:
2.5 m + 0.5 m + 2 m = 5 m above the liquid sodium pool surface. Hence the region where we are concerned about maintaining the NaK at a negative prssure with respect to its environment is at the bottom of the steam generator.
Between the center lines of its NaK connections the steam generator is 7.0 m tall.
There is a 16 inch X 16 inch 90 deg elbow off the induction pump inlet which takes up 24 inches of steam generator axis height.
On top of the induction pump there is 16 inch X 16 inch X 90 deg elbow to the horizontal cold pipe which takes up 24 inches of steam generator axis height.
There is 1.0 m between the axis of the hot horizontal pipe and the axis of the horizontal cold pipe.
Hence the height remaining for the induction pump is:
(7.0 m - 1.0 m - 24 inch) - (24 inch) = 6 m - 48 inch = 4.8 m remaining.
If we allow 16 inches = 0.4 m for the two induction pump end assemblies the remainder is 4.4 m long. That can be divided into 12.5 wound sections each 4.4 m / 12.5 = 0.352 m long.
INDUCTION PUMP DIMENSIONS:
HEAT EXCHANGE GALLERY LAYOUT:
Steam generator shell OD = 48 inch = 1.2 m
Between the horizontal NaK hot pipes feeding two adjacent steam generators spaced 1.5 m = 60 inch apart center to center runs a vertical 16 ____inch OD vent pipe. There are 4 layers of insulation.
Maximum insulation thickness is:
(60 - 16 - 16) / 4 = 7 inch
The steam generators are 48 inch = 1.2 m OD excluding insulation. Their flanges are 72 inch = 1.8 m OD. With insulation at the flanges the steam generators are 2 m OD.
The steam generator manifolds have flange connection faces that are 36 inches from the steam generator center line.
Allow 8 inches from the induction pump outer surface to the wall.
Thus the minimum heat exchange gallery width associated with the induction pump and its cold discharge pipe is:
8 inch + 48 inch = 56 inch.
Allow 8 inches from the wall to the hot pipe 16 inch X 16 inch X 16 inch tee flange.
Allow 24 inches from the hot pipe tee flange to the center of the tee branch. Then the tee is 48 inches long.
Thus the minium heat exchange gallery width associated with the feeding hot pipe is:
8 inch + 48 inch = 56 inch. Add a 40 inch corridor allowance nipple to make the total 96 inch.
The distance from the inner wall to the steam generators via the induction pump inlet is:
8 inch + 24 inch + 24 inch + 40 inch corridor = 96 inch
Then the distance from the inner wall to the first line of steam generator centers is:
96 inch + 36 inch = 132 inch = 3.3 m
The distance between the two lines of steam generator centres is:
[ (2 m)^2 - (1.5 m)^2]^0.5 = [1.75 m^2]^0.5 = 1.323 m ~ 1.4 m = 56 inch
Then the distance from the inner wall to the second line of steam generator centers is :
132 inch + 56 inch = 188 inch
Then the distance from the inner wall to the far side steam generator flanges is:
188 inch + 36 inch = 224 inch
The induction pump inlet vents each need a 24 inch long elbow attched to the far side of the lower steam generator manifold from the interior wall. This vent projects 32 inches, Hence the total projction from the inside wall is:
224 inch + 32 inch = 256 inches
Now allow for another 36 inch wide corridor to provide access to the steam valves. Then the total projection to the far edge of the corridor is:
256 inch + 36 inch = 292 inch.
Available gallery width = 8 m = 315 inch. That leave 23 inches for the steam lines near the outside wall. Allowing for 4 inches of steam line insulation leaves a maximum of 15 inch OD for the steam lines.
We need a 40 inch wide access corridor running between the induction pumps and the steam generators. This spacing is realized using 16 inch X 16 inch X 4 inch tee branch that is 40 inches long to connect between the steam generator lower manifold and the elbow feeding the bottom of the induction pump. The 4 inch OD branch goes down to the NaK dump tanks.
Note that space has yet to be allocated for steam valves, steamlines, condensate feed lines, instrumentation and the induction pump discharge vents.
HEAT EXCHANGE GALLERY LENGTH ALLOCATION:
With 72 inch diameter steam generator flanges the heat exchange gallery length requirement is:
5 (1.5 m) + 72 inch = 372 inch
The available heat exchange gallery length is:
10 m = 394 inches.
SUMMARY:
Steam generator shell is 48 inch OD, 6 m long,
Internal pressure = 10 MPa.
Main flange diameter = 72 inch
Steam Generator Manifolds each 1 m tall
Manifold subflange diameter = 32 inch
Pipe connection = 16 inch
Subflange location = 36 inches from steam generator center line
Steam generator tubes are Inconel similar to those in the intermediate heat exchange bundle.
For cooling the NaK is cooled down to less than 110 degrees C and hence cools the sodium pool down to about 120 degrees C, which permits fuel bundle repositioning and intermediate heat exchange bundle service.
The steam bypass valve from the steam generator to the turbine condenser is openned. Then evaportion of steam generator water will extract heat from the heat transfer fluid, the NaK and hence the sodium pool. The steam generator water level control system will automatically add replacement water as steam generator water evaporates.
The steam generator and the NaK induction pump are located in a heat exchange gallery outside the perimeter of the FNR's sodium pool enclosure. The NaK does not leave the nuclear island.
Note that a normally closed valve is requred for each dump tank system. On loss of house power this valve closes to prevent NaK flowing into the dump tank so as to preserve capability for emergency passive fission product heat removal.
NORMAL NaK FLOW VELOCITY
Now consider a NaK pipe with an inside diameter of 15.25 inches.(16 inch OD, 0.375 inch wall thickness)
The pipe cross sectional area is:
Pi (15.25 inch / 2)^2 X (0.0254 m / inch)^2 = 0.1178 m^2
Now assume a temperature drop across the NaK loop of:
450 C - 330 C = 120 C
Let V be the average axial flow rate of NaK through the NaK pipe. Then the thermal power transported by the NaK loop is:
P = V X 0.1178 m^2 X 0.9215 g / cm^3 X 10^6 cm^3 / m^3 X 120 C X 1.0368 J / g-C
= V X 13.510 X 10^6 J / m
From the reactor design:
P = 10^9 J / 48 s
Thus:
V = P / (13.510 X 10^6 J / m)
= [10^9 J / 48 s] / (13.510 X 10^6 J / m)
= 10^3 m / (48 X 13.510 s)
= 1.542 m /s
which is an acceptable NaK average axial liquid flow velocity.
NaK FILTERING:
FNR POWER CONTROL STRATEGY:
The control strategy is to use a variable speed induction pump to control the generated electric power. The return temperature of the NaK from the steam generator is set by the steam pressure at about 330 dgrees C. controlled at 330 degrees C. Due to the passive FNR temperature control the NaK supply temperature to the steam generator is nearly constant at 450 C.
The NaK return temperature is locked at about 330 C by the superheated water in the steam generator. The NaK supply temperature is locked at about 440 C by the FNR reactivity versus temperature characteristic. The reactor power is controlled by varying the speed of the induction pump. This ame controlsignal is used to set the power level of the steam generator jacket heater.
Note that this control arrangement relies on there always being some flow through the NaK loop to maintain temperature stability which means that normally the reactor output power should not be modulated down to zero. There will always be some natural circulation in the NaK loop due to fission product decay heat.
An advantage of this control strategy is that maintaining a constant high differential temperature across the NaK loop minimizes thermal stress during electric power modulation.
HEAT TRANSPORT LOOP ISOLATION:
There are 48 identical independent heat transport circuits, 6 connecting to each of the 8 heat exchange galleries located around the perimeter of the primary sodium pool. Failure of any individual heat transport circuit does not cause a failure of the whole. Likewise, any electricity generator can be operated at part power using only a fraction of its 6 allocated heat transport circuits.
Each intermediate heat exchanger supplies hot NaK to a dedicated steam generator. Each NaK loop has four parallel connected dedicated NaK dump tanks, a dedicated variable speed induction pump, a dedicated vacuum cushion tank and three dedicated NaK pressure relief vents. Any heat transport circuit can be shut down for service while the other heat transport circuits remain in operation.
Each of eight heat exchange galleries has six associated NaK heat transport loops. Each NaK heat transport loop must have the capacity:
1000 MWt / (6 X 8) heat transport loops = 20.833 MWt / heat transport loop
at a NaK differential temperature of:
100 degrees C to 120 degrees C.
Each heat transfer loop transfers up to 20.833 MWt of heat which in turn can be used to provide:
20.833 MWt X 0.300 = 6.25 MWe
of turbo-electricity generation. Thus the maximum possible system electricity output is limited by the available heat transport circuits to about:
(48) X 6.25 MWe = 300MWe
Each NaK heat transport loop is executed using 16.000 inch OD schedule 40S stainless steel pipe. This pipe has a wall thickness of 0.375 inch and a linear weight of 75 lb / ft.
At full load the differential temperature drop across each NaK pipe loop is about 110 degrees C and the maximum NaK fvolumetric low in each pipe is ~ 0.274 m^3 / s.
NaK DUMP TANK SIZING:
Asume that the dump tanks are the maximum pressure limiting devices in the NaK circuit.
Assume that the NaK dump tanks are made from 3 m long pieces of 48 inch OD, 0.5 inch wall stainless steel pipe.
W = wall thickness = 0.5 inch
S = wall hoop stress
Sy = wall hoop yield stress at 600 deg C = 117 MPa
P = differential pressure
Py = pressure corresponding to Sy
S = [(48 inch - 2 W) / 2 W] P
or
Py = Sy [2 W / (48 inch - 2 W)
= 117 MPa / 47
= 2.489 MPa
Hence the maximum safe working pressure Pw in the NaK circuit is:
Pw = Py / 3
= 2.489 MPa / 3 = 0.83 MPa
Assume the induction pump has 16 inch OD X 0.25 inch wall material.
Sw = (15.5 inch / 0.5 inch) 0.83 MPa
= 25.73 MPa
which is less than:
Py / 3 = 117 MPa / 3
= 39 MPa.
Note that the dump tanks contain argon volumes that attenuate NaK pressure pulses.
The cross sectional open area of the proposed NaK dump tank material is:
Pi[47.0 inch /2]^2 X [0.0254 m / inch]^2 = 1.11932 m^2.
Thus the maximum available NaK dump tank volume is:
4 tanks X 3 m high X 1.11932 m^2 = 13.432 m^3
Assume 4 insulated dump tanks in a tight row.
Assume 2 X 0.25 m for end insulation
Assume 3 X 0.5 m = 1.5 m for intertank spacing
Assume 4 X 48 inch X.0254 m / inch = 4.9 m for tanks
.
Thus the width required = 0.5 m+ 1.5 m + 4.9 m = 6.9 m
Each tank row with its insulation is about 1.42 m in depth. Without insulation tanks are 1.3 m wide at tops and bottoms allowing vertical lift removal.
NaK PIPE CONSTRUCTION:
The NaK piping is 16 inch schedule 40S pipe ( 0.375 inch wall).
Assume 90 degree elbows have an 16 inch inside radius of curvature and a 32 inch outside radius of curvature.
The flanges for 16 inch OD pipe are 32 inch OD Insulation thickness = 4 inch
For the cool pipe:
Find distance from pool wall to center of intermediate heat exchange bundle gooseneck riser:
4 + 64 -8 = 60 inch
Hence the manifold centers are on a circle: 20 m - 2(1.5m) = 17.0 m in diameter
The maximum manifold radius permitted by the down pipe and goose neck is:If all of these manifolds are on the same circle they must not clash.
Circle circumference = Pi (17.0 m) = 53.40 m, allowing:
53.40 / 56 = 0.9537 m / intermediate heat exchange manifold = 37.55 inches
Note that the inside edges of the manifolds are on a circle:
20 m -4 m = 16.0 m in diameter
******************************
The NaK dump tanks are formed from 48 inch outside diameter stainless steel sheet with 0.75 inch thick walls.
REQUIRED NaK VOLUME:
The cross sectional area of the 15.25 inch I.D. pipes is:
Pi (15.25 inch / 2)^2 X (.0254 m / inch)^2
= 0.1178 m^2
The overall length of equivalent 16 inch pipe containing NaK is:
58.35 m.
The equivalent 16 inch OD pipes have a contained NaK volume of:
58.35 m X 0.1178 m^2 = 6.874 m^3
The intermediate heat exchange bundle contains a NaK volume of 1.0595 m^3.
The steam generator contains a NaK volume of 3.3869 m^3.
FIXHence the NaK dump tank capacity must be more than:
6.874 m^3 + 1.0595 m^3 + 3.3869 m^3 = 11.320 m^3
We have not accounted for the vent pipe or drain down pipe volumes. Prudence suggests that we design for some excess NaK dump tank capacity.
OVERALL NaK REQUIREMENT:
The previous calculation indicates that in sourcing NaK we must plan on acquiring:
48 heat transport circuits X 12 m^3 NaK / heat transport circuit = 576 m^3
of NaK.
MAINTENANCE:
There is no radioactivity in the heat exchange galleries which allows safe service work or NaK fire suppression in selected heat exchange galleries without causing a total reactor shutdown.
PLAN VIEW
Note the 2.0 m wide space between adjacent heat exchange galleries that is dedicated to the airlocks that are required for moving fuel bundles and intermediate heat exchange bundles from their truck load/unload points into or out of the sodium pool space.
DIAGRAM:
A diagram showing an end view of a heat exchange gallery. Each gallery has 6 heat transport loops, one behind the other. Note that the steam generators are staggered in position, so that part of the 2nd loop is visible behind the first loop.
HEAT EXCHANGE GALLERY:
The left hand side of this diagram shows the intermediate heat exchange bundle and the NaK pipes. This diagram shows the steam generators on the right hand side and the three parallel connected NaK dump tanks in the lower right middle. The vertical induction pump, the NaK flow meter are in the middle of the diagram. Above the steam generator from left to right are the induction pump discharge NaK column, the intermediate heat exchange bundle discharge NaK column and the induction pump inlet NaK column.
Note that steam generator staggering enables a steam generator flange diameter of 72 inch = 1.8 m. Note that the steam generator centerline to end wall clearance is 1.25 m which is sufficient for the steam generator end manifold flanges + insulation with a 48 inch OD shell.
Each heat exchange gallery has a lower level where the NaK dump tanks are located. Personnel access to the various heat exchange gallery levels is via a stairwell at the gallery end farthest from the airlock truck load/unload point.The disconnects for the NaK induction pumps are wall mounted adjacent to the induction pumps.
Equipment in the heat exchange galleries is installed and removed from above using a mobile crane parked at the airlock truck load/unload point. The roof over the heat exchange galleries must be easily removable and replaceable.
There must be a large air vents in heat exchange galleries for outside air cooling.
An important issue in the heat exchange gallery is isolation of potential NaK drips. Drip collection pans should be provided to isolate dripped NaK. Note that these drips will self ignite in air.
In the basement under each heat exchange gallery is an isolated space that is used for an argon bladder. This space is air flow connected to the service access space under the pool deck. Any water penetrating this space must flow along the floor and into the FNR bottom drain located about 18 m below grade.
NaK PIPING:
The intermediate heat exchanger is counter flow and is realized with a single pass vertical tube bundle.
The intermediate heat exchange bundle tube side top manifold connects to the steam generator tube side top manifold via 16 inch OD schedule 40S stainless steel pipe. The intermediate heat exchange bundle bottom connects to the steam generator tube side bottom via a 16 inch OD schedule 40S stainless steel pipe. This pipe contains an induction pump that circulates NaK from the bottom manifold of the steam generator to the bottom manifold of the intermediate heat exchange bundle. This configuration provides heat exchange counterflow and permits removal and replacement of individual steam generators and induction pumps via an overhead crane lift. There is a gravity drain to three parallel connected NaK dump tanks. A small top shared pipe loop is still required for each NaK circuit to trap and expel gases and to indicate the NaK level.
MAXIMUM SAFE NaK WORKING PRESSURE:
For the NaK 16 inch OD schedule 40S pipe used in the induction pump the ID is:
15.25 inch
The NaK pipe wall thickness is:
0.375 inch
Assume that the induction pump barrel is made of SS pipe. A table of 316 SS yield stress versus temperature is as follows:
TEMPERATURE (degrees K) | YIELD STESS (MPa) |
300 | 208 |
400 | 167 |
500 | 144 |
600 | 129 |
700 | 122 | 900 | 114 |
1000 | 104 |
The highest anticipated NaK working temperature is:
520 C + 273 = 793 K
which from the above table indicates a 316 SS yield stress of 117 MPa.
The corresponding maximum 316 SS working stress is:
117 MPa / 3 = 39 MPa.
NaK PIPING PRESSURE RATING
At 600 degrees C the yield stress of stainless steel is 117 MPa.
Assume the use of 18 inch OD, 17.25 inch ID pipe for the NaK induction pump flow tube. The flow cross sectional area of each such pipe is:
Pi (6.000 inch)^2 X (.0254 m / inch)^2 = 0.07296 m^2
The pipe yield stress at 600 deg C is 117 MPa.
117 MPa X (2) X (0.3750 inch)X L = 87.75 MPa inch L
Hence for safety the NaK pipe working stress should be less than:
117 MPa / 3 = 39 MPa
In the induction pump the OD = 18.00 inch.
The induction pump barrel working pressure at 600 deg C is:
39 MPa X 2 (0.375 inch) = 17.25 inch X P MPa
Hence for safety the NaK pipe working pressure should be less than:
P = 39 MPa X 2 X (.375 inch / 17.25 inch)
= 1.6956 MPa ~ 1.7 MPa
PIPE WALL SEALING AND SUPPORT:
Flexible air and argon bellows wall seals are required at locations where the NaK pipes pass through the inner reactor enclosure wall to accommodate thermal expansion/contraction. Under ordinary operation the reactor power is modulated by controlling the nitrate salt circulation rate and hence the NaK circulation rate. This control methodology causes significant loop differential temperatures.
The NaK pipes and the induction pump must be supported with threaded support hardware so that the pipes and pump remain in their correct positions when an intermediate heat exchanger is disconnected.
NaK TEMPERATURE CONSTRAINTS:
Inside the tubes of the intermediate heat exchange bundle is non-radioactive NaK normally at a pressure less than 0.1 MPa. The normal low temperature limit on the circulated NaK at full load is 330 degrees C to prevent NaOH precipitation on the inside of the tubes within the NaK-salt heat exchanger and to prevent nitrate salt solidification. The normal high temperature limit on the circulated NaK is ~ 460 degrees C. We are assuming a full load 10 degree C temperature difference across the intermediate heat exchange tube bundle wall. At full load the dry steam in the steam generator will reach about:
(460 deg C - 10 deg C -10 C - 40 deg C) = 400 deg C.
At full load the NaK temperature differential is:
450 -330 = 120 deg C
without threat of NaOH precipitation. There is feed water temperature mixing in the lower part of the steam generator to minimize thermal stress on the lower ends of the steam generator tubes. The injection water temperature rise from 25 deg C to 320 C is realized by feed water recuperator heat recovery from the steam immediately upstream from the turbine condenser followed by water mixing in the bottom of the steam generator shell.
TEMPERATURE CONSTRAINT:
At low steam loads the NaK discharge temperature from the intermediate heat exchange bundle will rise to about 459 degrees C. As the steam load increases the NaK discharge temperature from the intermediate heat exchange bundle will decrease to about 450 degrees C.
INDUCTION PUMP THERMAL PROTECTION:
Induction pumps are used to circulate the NaK. The induction pumps must be sized to overcome the flow pressure head in the NaK loops. Note that these pumps should be located on the low temperature return pipes near the primary sodium pool deck level to ensure both cool operation and sufficient positive suction head.
The induction pump operates by inducing a circular current in the liquid sodium. This current crosses a radial magnetic field component and hence experiences an axial force. External 3 phase coils, analogous to the stator coils of a 3 phase AC motor, create a suitable time varying magnetic field.
In normal operation the pumped NaK temperature at the induction pump is in the temperature range 330 degrees C and the induction pumps are oil cooled to protect the electrical insulation from heat damage.
However, under circumstances when the steam generator contains no water the NaK temperature at the induction pump can potentially rise to about 460 degrees C. Under these circumstances the induction pump can easily be damaged if it has insufficient pumped oil cooling. To prevent wide temperature excursions the steam generator shouldbe charged with water before the NaK is transferred from its dump tank back into the NaK heat transfer loop.
Induction pump details are set out at FNR Induction Pump.
GASKET CONSTRAINT:
This FNR operates at too high a (temperature X pressure) product for use of normal elastomeric gaskets. Soft metal or compressed carbon gaskets must be used. Such gaskets do not tolerate pipe misalignment, manifold distortion or high pressures. Hence gasketed mechanical joints need near optical precision fabrication. All the NaK flanges are sealed with such gaskets.The flange bolts must have a smaller TCE than the flange material.
THERMAL EXPANSION:
The steam generators are in fixed positions with respect to the concrete structure. The intermediate heat exchange bundles move radially due to connecting pipe thermal expansion and contraction. Also the above pool deck sodium pool inside wall moves due to thermal expansion. When the system is cold the insulation of the cooler intermediate heat exchange bundle supply pipes should be almost touching the sodium pool inside wall. When the system is hot there is about a 0.2 m gap between this pipe insulation and the sodium pool inside tank wall.
NaK FLOW:
Some of the FNR NaK flow issues are discussed in the paper titled Improving SFR Economics Through Innovation.
The FNR NaK loops take advantage of the relatively large thermal coefficient of expansion of liquid sodium to promote natural circulation of the NaK.
Hence the NaK flow rate for the entire reactor is:
0.274 m^3 / s X 48 = 13.152 m^3 / s
which must be matched by the sodium flow rate.
Herein lies a potential problem. To provide the same heat flux with a 60 degree C sodium temperature differential the total sodium flow must be almost twice as great.
If the total available sodium flow rate through the fuel asembly is less than 26.304 m^3 / s it may constrain the reactor thermal output power.
In normal operation hot (460 degree C) primary sodium flows into the intermediate heat exchange bundles just below the pool surface, flows down outside the intermediate heat exchange tubes and is discharged about 6 m below the primary sodium pool surface at a temperature of about 340 degrees C. Simultaneously NaK flows up inside the intermediate heat exchange bundle tubes, entering at about 330 degrees C and leaving at about 450 degrees C.
The intermediate heat exchange bundles are single pass to realize counter current operation and to minimize material thermal stresses.
In the steam generator NaK flows downwards inside the tubes while water/steamflows upwards in the shell.
Potential fire problems are NaK micro-leaks from the heat transport piping, intermediate heat exchange bundle or induction pump. The NaK pressure driving such leaks is negative. In every case the fire can be extinguished by releasing the argon pressure over the NaK dump tank to the overhead vacuum space which causes gravity drain down of the NaK into the NaK dump tanks.
INTERMEDIATE HEAT EXCHANGE BUNDLES:
The intermediate heat exchange bundles isolate the radioactive liquid sodium from the NaK. The intermediate heat exchange bundle also serve as a barrier to other radioactive species in the event of a fuel tube leak.
To attain the desired full load temperature distribution in the intermediate heat exchanger bundles the NaK mass flow rate must match the sodium mass flow rate. However, the sodium flow cross sectional area is larger so the average sodium linear descent velocity is smaller.
There is a ring of 48 intermediate heat exchange bundles that are immersed in the sodium pool in a 18 m OD, 16 m ID ring. The heat exchange tubes are located between the pool surface and 6 m below the pool surface.
The weight of the intermediate heat exchange bundles is supported by a ring shaped table located in the sodium pool about 8 m above primary sodium pool bottom and 8 m to 9 m radially from the pool center. This table is supported by a ring of steel columns and the table is horizontally stabilized by interleg connections and by the adjacent innermost steel cup sodium pool liner. The top of this table is flat to allow the supported intermediate heat exchange bundles to slide back and forth radially over a distance of about 0.2 m to accommodate thermal expansion/contraction of the sodium pool and the radial NaK piping. Apart from thermal expansion the radial position of the intermediate heat exchange bundles is fixed by the radial NaK pipes which in turn are fixed to the stem generators and induction pumps, which are in turn are fixed to the heat exchange gallery steel and concrete structure. Thermal expansion, at points where these pipes pass through gas tight walls, is accommodated by use of metal bellows fittings.
The maximum outside diameter of the intermediate heat exchange manifolds is limited to:
37.25 inches
so that after accounting for thermal expansion 56 of them will fit in the available space on an 18 m diameter circle in the primary sodium pool. Note that with thermal expansion the circle shrinks to 17.6 m diameter.
DETECTION OF NaK LEAKS:
Any leak in a NaK circuit will result in loss of NaK volume in the NaK loop. Should such a volume drop occur that entire heat transport circuit should be shut down, the molten salt drained to its dump tank and the
NaK drained to its the dump tank.
NaK FLOW PATH:
This configuration balances flows, optimizes heat transfer and minimizes thermal stresses. The standard piping connection arrangement for each NaK circuit starting at the induction pump discharge: 1 X 16 inch 90 degree elbow, 1 X straight, the intermediate heat exchanger lower manifold, the intermediate heat exchange tubes, the intermediate heat exchanger upper manifold, 1 X 16 inch straight pipe, 1 X 16 inch tee, the steam generator upper manifold, the steam generator tubes, the steam generator lower manifold, 1 X 16 X 16 X 16 inch tee, 1 X 16 inch X 16 inch X 4 inch tee down to a NaK dump tank, and a 16 inch X 90 degree elbow connection to the induction pump inlet. There is one small drain/fill valve for each heat exchange loop. This arrangement permits practical and safe identification, isolation, draining, replacement and refilling of any defective heat transport loop component.The pipes must have sufficient positioning play to allow for thermal expansion-contraction and possible earthquake related movement.
MANIFOLD VENTING
Both the upper and lower manifolds of each steam generator have 16 inch diameter pressure relief vents to an overhead vacuum space. Each lower manifold vent needs 2 X 16 inch 90 degree elbows to avoid other overhead pipes. In the event of a sudden steam generator tube faoilure these vents relieve the sudden pressure rise first into the vacuum space and then to the outside via a shared rupture disk.
INDUCTION PUMP DISCHARGE VENT
The induction pump discharge vent connects via a custom fitting to the 16 inch X 16 inch X 16 inch tee at the induction pump discharge.
NaK VOLUME:
The volume of each NaK loop can be estimated by assuming that everywhere along that loop except in the heat exchange manifolds the cross sectional area is approximately the same as the cross sectional area of a 16 inch schedule 40S pipe.
Thus the minimum NaK pipe length equivalents are:
Intermediate heat exchange tubes = 6 m
Intermediate heat exchange riser = 8 m
Intermediate heat exchange connectors = 4 m
NaK-salt heat exchange tubes = 6 m
NaK-HTF heat exchange tubes = 6 m
Inter Heat Exchanger connector tube = 8 m
Intermediate heat exchange riser = 8 m
Induction pump = 10 m
6 Manifolds @ [1.1 m X Pi (0.4 m)^2] = 3.317 m^3 /0.073 m^2 = 45.44 m
Room riser = 11 m
Room connector = 3 m
Hence total equivalent pipe length = 115.44 m
NaK volume = 115.44 m X 0.073 m^2 = 8.427 m^3
Required minimum NaK dump tank volume = 9 m^3
DUMP TANKS:
At the low points in the heat transport pipe loops are dump tanks with sufficient volume to accommodate all the NaK in that heat transport loop. Note that the NaK dump tanks must be rated as pressure vessels and must be fitted with high pressure argon relief valves vented to the argon atmosphere over the sodium pool. Note that changing the temperature of the argon in the dump tank affects the argon pressure and hence the NaK level. Hence each NaK loop needs its own argon pressure control and NaK level sensor for liquid level regulation.
The NaK level control relies on argon pressure control by external low temperature argon valves. To charge the NaK loop argon is first injected into the top of the dump tanks while the displaced argon in the cushion tank is vacuum extracted to the sodium pool space.
This arrangement requires a reliable valves on small argon pipes connected to the dump tank that either vent the dump tank to the argon atmosphere or connect pressurized argon to drive NaK out of the NaK dump tank. Note that over time NaK vapor may tend to condense in the cooler vent line. This issue may require ongoing maintenance.
DETECTION OF NaK LEAKS:
Any leak in a NaK circuit will result in loss of NaK volume in the NaK loop. Should such a volume drop occur that entire heat transport circuit should be shut down and the NaK drained to its dump tank.
NaK FIRES:
Other parties using NaK for heat transport have experienced repeated fires. The problem is that if hot high NaK is inside a pipe the NaK tends to leak out via any mechanical joint that is less than perfect. The NaK operating temperature is too high for use of conventional elastomeric gaskets. Once outside the pipe the NaK spontaneously ignites in air. That situation is unacceptable.
The solution to this problem is to operate the NaK at less than atmospheric pressure and to fit every NaK loop with a dedicated dump tank. At the first hint of a fire, release of the argon pressure over the relevant dump tanks causes the NaK in the affected loop to immediately drain down into its NaK dump tanks. This procedure will quickly asphyxiate a NaK fire. Any NaK dribble in a heat exchange gallery can be extinguished using a Na2CO3 fire extinguisher.
WATER FOR DECAY HEAT REMOVAL:
There must be enough reliable water available at the steam generators to remove the fission product decay heat by evaporation of that water.
EROSION:
We need to be concerned about long term erosion of the NaK enclosing materials and precipitation caused by impurities Na2O, NaOH, K2O and KOH in the NaK. A relevant reference is corrosion by caustic soda.
We anticipate the need for side arm filters across the induction pumps to continuously remove solid granular material.
The filter changing apparatus will require pressurized argon.
PROVISIONS FOR SYSTEM MAINTENANCE:
To enable heat transport system service the NaK is transferred into its dump tank.
Application of argon pressure over the NaK dump tank and relief of argon pressure from the top of the NaK loop transfers Nak from the dump tanks into the NaK loop. Reversing this procedure allows the NaK to gravity flow back into its dump tanks.
A NaK level sensor should be provided at the top of each NaK loop to indicate when to close the system fill valve. The supply of argon for presurizing the Nak dump tank and the argon sink from the system top can both be from the primary sodium pool enclosure. Similarly when NaK drain down to its dump tank is required the argon in the dump tank can be vented to the primary sodium pool enclosure and after the argon pressure has sufficiently dropped the argon top vent valve can be openned. Note that for safety this argon top vent valve must be vented over the primary liquid sodium pool.
To expel NaK from the intermediate heat exchanger tubes the NaK level is first drained down to the level of the bottom of the return pipe to the intermediate heat exchanger. Then a blanking disk is installed between the flanges of the intermediate heat exchange bundle NaK discharge pipe. Then argon pressure is applied to the intermediate heat exchange discharge which will drive most of the contained NaK from the intermediate heat exchange bundle into the dump tank.
In reality, even after this procedure is complete a small amount of NaK will remain in the bottom manifold of the intermediate heat exchange bundle and the bottom manifold of the NaK-salt heat exchanger. This small NaK accumulation presents a potential risk to maintenance personnel and a potential fire risk if at some later time oxygen is admitted into the NaK piping. This risk can be minimized by use of a small tube that connects onto the bottom of the intermediate heat exchange bundle lower manifold and removes the remanent NaK by vacuum suction. In general for safety the flange connections of the intermediate heat exchange bundle and the radial piping should be closed with blanking plates while the intermediate heat exchange bundle is still in the argon atmosphere over the primary sodium pool.
PROTECTION OF THE NaK LOOP FROM HIGH TRANSIENT PRESSURES:
In the event of a steam generator tube failure there is potential for a violent chemical reaction between the NaK and water/steam. This chemical reaction will cause a rapid transient rise in the NaK loop pressure which if not properly managed could cause a liquid NaK pressure pulse analogous to water hammer, potentially rupturing the intermediate heat exchange bundle and possibly leading to major facility damage. Hence the NaK loop must be designed to safely withstand large transient pressures and the NaK should normally operate at a pressure of less than 0.1 MPa. Sustained high pressure is prevented by venting the NaK loop to the atmosphere and by dropping the liquid NaK into its dump tank at the first hint of trouble.
In order for the safety mechanisms to reliably function there must also be a mechanism that can provide instantaneous NaK pressure relief. That rate is limited by the maximum NaK flow through the steam geneator tube failure which rate is a function of the heat exchange tube inside diameter and the vent diameter.
In a practical accident scenario the chemical reaction forms hydroen which rapidly raises the NaK pressure. The hydrogen is vented via a 16inch OD pressure relief vent.
Each NaK heat transport loop is normally at less than 0.1 MPa. The NaK dump tank also acts as an expansion tank that partially attenuates any pressure pulse in the NaK.
CONSTRAINTS:
1) There must be enough NaK natural circulation to dependably remove fission product decay heat so that the system remains safe on loss of electric power to the NaK induction pumps.
2) Need thick concrete walls between the sodium pool and the heat exchange galleries to protect workers in the heat exchange galleries from gamma radiation emitted by spontaneous decay of Na-24 into Mg-24.
These same walls provide structural support of the gantry crane and the dome roof.
CALCULATE NaK VISCOUS PRESSURE DROP AT SUFFICIENT NATURAL CIRCULATION TO REMOVE FISSION PRODUCT DECAY HEAT:
An important issue with the intermediate heat exchange bundles is their ability to remove fission product decay heat by natural circulation. In natural circulation the NaK flow rate is low and laminar, so the heat transfer characteristics are different from when the NaK loop is pumped. It is necessary to have a sufficient number of intermediate heat exchange tubes to allow the required natural circulation and laminar flow limited heat transfer. The viscosity of the NaK must be taken into account.
The following equations derived on the web page titled FNR PRIMARY SODIUM FLOW can be used to find the natural circulation volumetric fluid flow Fv per round coolant flow channel.
Fv = {Pi Pg Ro^4 / [Muv Zo (N + 2)(N + 4)]}BR>
where:
Pi = 3.14159
Pg ~ 1000 Pa
Ro = (0.37 inch / 2) X (0.0254 m / inch) = 0.004699 m
Muv = 3 X 10^-4 N-s / m^2
(N + 2) = Ro [(Rhos Pg) / 2]^0.25 [1 / [Muv Zo]^0.5]
where:
Zo = 6.0 m
Rhos = 849.4 kg / m^3
Numerical substitution gives:
(N + 2) = Ro [(Rhos Pg) / 2]^0.25 [1 / [Muv Zo]^0.5]
= 4.699 X 10^-3 m [(849.2 kg / m^3) (1000 kg m /s^2 m^2) / 2]^0.25 [1 / [(3 X 10^-4 N^-s / m^2)(6 m)]^0.5]
= 4.699 X 10^-3 m [25.5267 kg^0.5 / s^0.5 m] [ 1 / [4.24264 X 10^-2 (kg m s /s^2 m)^0.5]]
= 2.8272482 kg^0.5 s-0.5 kg^-0.5 s^0.5
= 2.8272482
Hence the NaK natural circulation flow Fv through each tube is given by:
Fv = {Pi Pg Ro^4 / [Muv Zo (N + 2)(N + 4)]}
= {3.14159 (1000 N / m^2)(0.004699 m)^4 / [(3 X 10^-4 N - s / m^2) (6 m) (2.8272)(4.8272)]}
= {3.14159 (1000)(487.55294 X 10^-12 m^2 / [(245.654277 X 10^-4 s / m)]}
= 6.23515 X 10^-5 m^3 / s
With 800 ______ tubes intermediate heat exchange / bundle the NaK natural circulation flow rate is:
800 tubes/bundle_____ X 6.23515 X 10^-5 m^3 / s-tube = 0.06378 m^3 / s
which is faster _________than the minimum required natural circulation rate.
VISCOSITY
FIX!The corresponding NaK flow rate in the intermediate heat exchange bundle tubes is:
(321.05 m^2 / hr-exhanger) / (823 tubes / exchanger) = 0.3900 m^3 / hr-tube
= (0.3900 m^3 / hr-tube) X (1 hr / 3600 s)
= 1.08333 X 10^-4 m^3 / s-tube
The corresponding NaK flow rate in the steam generator tubes is:
(321.05 m^3 / hr-exchanger) / (625 tubes / exchanger)
= 0.51368 m^3 / hr-tube
= (0.51368 m^3 / hr-tube) X (1 hr / 3600 s)
= 1.4268 X 10^-4 m^3 / s-tube
The following equations derived on the web page titled FNR PRIMARY SODIUM FLOW can be used to find the pressure drop Pd per round coolant flow tube neglecting natural circulation:
Fv = [Pi Pd Ro^4] / [Muv Zo (N + 2)(N + 4)]BR>
where:
Pd = pressure drop along tube in Pa (1 Pa = 1 kg m /s^2 m^2)
Fv = volumetric flow rate / tube
Pi = 3.14159
Ro = (0.37 inch / 2) X (0.0254 m / inch) = 0.004699 m = tube inside radius
Muv = 3 X 10^-4 N-s / m^2 = sodium viscosity
(N + 2) = Ro [(Rhos Pd) / 2]^0.25 [1 / [Muv Zo]^0.5]
where:
Zo = 6.0 m = tube length
Rhos = 849.4 kg / m^3 = density of sodium at the reactor operating temperature
Recall that:
Fv = [Pi Pd Ro^4] / [Muv Zo (N + 2)(N + 4)]
or
Pd = [Fv / (Pi Ro^4)] [Muv Zo (N + 2)(N + 4)] Equation #1
Recall that:
(N + 2) = Ro [(Rhos Pd) / 2]^0.25 [1 / [Muv Zo]^0.5]
or
N = {Ro [(Rhos Pd) / 2]^0.25 [1 / [Muv Zo]^0.5]} - 2 Equation #2
Try and initial interim value of N = 1.0 in equation #1 and solve for an interim value of Pd.
Substitute that interim value of Pd into equation #2 and solve for a new interim value of N.
Repeat this process itteratively until N and Pd converge.
Then the sum of the Pd values in combination with the exchanger intermediate sodium flow rate give the mechanical load for an ideal circulation pump.
This intermediate liquid sodium flow will develop a momentum change pressure at a sharp 90 degree elbow of:
(2.010 m / s)^2 X 1 m^2 X 927 kg / m^3 = P X 1 m^2
or
P = (2.010 m / s)^2 X 927 kg / m
= 3746 kg / m s^2
= 3746 Pa
= 3746 Pa X 1 bar / 101,000 Pa
= 0.03709 bar
This pressure change is one possible method of measuring the fluid velocity in the pipe.
BOUNDARY LAYER TEMPERATURE DROP
However, there will be a reduction in intermediate heat exchanger performance because the primary side of the intermediate heat exchanger operates in the laminar flow region. The effective tube wall thickness is increased by about (1 / 8) inch of sodium. At 700 deg K the liquid sodium has a thermal conductivity of 70.53 W / m-deg K.
Hence the temperature drop delta T across the (1 / 8) inch thick liquid sodium boundary layer is given by:
875 X 10^6 Wt / 56 bundles = [(delta T) (70.53 Wt / m-deg K) X 823 tubes X 6 m X Pi X (0.5 inch) / (1 / 8)] inch
or
(delta T) = [875 X 10^6 Wt / [(56 bundles) X (70.53 Wt / m-deg K) X (823 tubes / bundle) X 6 m X Pi X (0.5 inch) / (1 inch / 8)]
= 3.57 deg K
The web page FNR HEAT EXCHANGE TUBES
indicates that at full rated power the temperature drop across the intermediate heat exchanger tube metal wall is 7.40 deg C. Hence the total temperature drop across the intermediate heat exchange bundles at full power is about:
3.57 deg C + 7.40 deg C = 10.97 deg C.
MATERIAL CONSTRAINT:
As the liquid sodium flows through the fuel asembly at full power its temperature increases from 400 C to 460 C. In this temperature range in a fast neutron flux the fuel tube material HT-9 undergoes goes material embrittlement if it contains any nickel.
NaK VENT PIPES
The NaK vent pipes are 16 inch OD. Above the NaK column peak level is a tee followed by a straight evacuated section. The branch off the tee goes upward to a ball check and a rupture disk. The three vent pipes associated with a single heat transport loop are connected together using smaller pipe that goes to a common vacuum pump. The vacuum pump discharge goes to a cold trap for exhausted material recovery.
INSTALLATION:
Each heat exchange gallery has an internal length of 10 m and an internal width of 8.0 m. There is 1.5 m between adjacent loops. There is a 1.25 m clearance at each end.
Equipment in theupper portion of the heat exchange galleries is lowered by crane from above. The steam generators and induction pumps are very heavy. Each steam generator-induction pump pair is supported by at least one dedicated 10 m long I beam. Each heat transport loop has dedicated NaK dump tanks on the floor below, again supported by dedicated 10 m long I beams. The dump tanks are each made from 4 X 48 inch diameter steel cylinders. There is space near the outside wall for below grade high pressure steam and and condensate return lines. The lower floor is accessed via corner stairwells. Dump tanks are lowered by crane through 2 m wide pool deck corner holes.
An important issue in the heat exchange gallery basement is separation of seepage water and potential NaK drips. Water is only likely to seep in near the outside wall. Elsewhere there could be NaK drips. A cement ridge should be provided across the basement floor to separate these two accumulations.
As a rule of thumb electrical equipment should be mounted on inside walls which are less subject to water penetration. There will need to be a large air vent in the access stair well end wall for air cooling.
The heat exchange gallery basement water sump pump should flow to a bottom drain at 18 m below grade.
MICROLEAKS:
A significant issue with the NaK loop design is microleaks. The NaK operates at a lower pressure than its surrounding fluids so there is a tendency for surrounding fluids to gradually leak into the NaK. In the space above the sodium pool argon tends to leak into the NaK loop. This argon will tend to collect in the vacuum space above the NaK columns.
Under the surface of the sodium pool Na will tend to leak into the NaK loop. That leakage will manifest itself as a long term increase in the ratio of Na to K in the liquid NaK alloy.
In the heat exchange galleries air will tend to migrate into the NaK. The air contains nitrogen and oxygen. The nitrogen will tend to collect in the vacuum space above the NaK columns. The oxygen will chemically combine with NaK to form Na2O and K2O. These oxides have a higher density than NaK and will tend to collect in the lower manifold of the steam generator.
In the steam generator high pressure water tends to leak into the low pressure NaK. This water will flash into steam and will chemically combine with the NaK to form H2 gas, NaOH and KOH. The NaOH and KOH both have higher densities than NaK. Above 406 degrees C KOH is liquid. Above 318 degrees C NaOH os liquid. As the NaK cools these impurity compounds will tend to collect in the lower manifold of the steam generator. The hydrogen gas will tend to collect in the vacuum space above the NaK columns.
Due to the high NaK temperatures Na vapor and K vapor will tend to collect in the vacuum space above the NaK columns.
In order to maintain the NaK column height in is necessary to periodically extract gases from the vacuum space over the NaK columns.
In order to set the height of the NaK columns, it is necesary to adjust the argon pressure over the dump tanks. Note that the height of the NaK coloumns is also dependant on the NaK temperature, NaK fill quantity, NaK density, Ar pressure above the NaK dump tank and gas and vapor pressure above the NaK columns.
Generally each NaK loop will require periodic use of a vacuum pump and occsional adjustment of the Ar pressure over the NaK dump tanks.
STEAM GENERATOR TUBE FAILURE:
If there is a sudden steam generator tube failure a jet of high pressure water or steam is will be injected into the NaK. This process will rapidly produce both steam and hydrogen gas. These gases can propel existing NaK columns up the 16 inch OD vents like water hammer. The evacuated portions of the vents should extend straight up for at least 11 m. The top of each vent must be strong enough to safely absorb the fluid hammer. Near the bottom of the evacuated tees with branches fitted with ball checks and rupture disks.
We must calculate the maximum H2O injection rate into the NaK and the consequent rate at gas formation displaces NaK. We must compare the maximum gas production rate to the maximum vent NaK discharge rate.
HYDROGEN VENTING:
Consider H2 gas. At 273 K, 0.1 MPa it occupies 22.4 litres / mole = [0.0224 m^3 / .002 kg]
At 500 deg C, 0.1 MPa H2 occupies:
[(500 + 273) / 273][0.0224 m^3 / .002 kg] = 31.71 m^3 / kg
At 1.7 MPa H2 occupies:
31.71 / 17 = 1.865 m^3 / kg
so its density is:
1 / 1.865 = 0.5362 kg / m^3
Recall that:
(differential pressure) = density X (velocity)^2 / 2
or
(Velocity) = [2 (differential pressure) / density]^0.5
and
(mass flow rate) = (density) X (area) X (velocity)
= [2 (density) X (differential pressure)]^0.5 X (area)
Hence the maximum 500 deg C hydrogen gas vent rate out a 16 inch diameter vent is:
[2 (density) X (differential pressure)]^0.5 X (area)
=[2 (0.5362 kg / m^3)X (1,600,000 Pa]^0.5 X (0.1178 m^2)
= 154 kg / s
STEAM VENTING:
Consider H2O vapor. At 273 K, 0.1 MPa H2O occupies:
22.4 litres / mole = [0.0224 m^3 / .018 kg]
At 500 deg C, 0.1 MPa steam occupies:
[(500 + 273) / 273][0.0224 m^3 / .018 kg] = 3.5233 m^3 / kg
At 500 deg C, 1.7 MPa steam occupies:
3.5233 / 17 = 0.20725 m^3 / kg
so its density is:
1 / .20725 = 4.825 kg / m^3
At 500 degree C, 10 MPa steam occupies:<
3.5233 m^3 / (kg 100) = 0.03523 m^3 / kg
or steam density is:
28.384 kg / m^3.
Recall that:
(differential pressure) = density X (velocity)^2 / 2
or
(Velocity) = [2 (differential pressure) / density]^0.5
and
(mass flow rate) = (density) X (area) X (velocity)
= [2 (density) X (differential pressure)]^0.5 X (area)
Hence the maximum 1.7 MPa, 500 degree C steam vent rate out a 16 inch diameter vent is:
[2 (density) X (differential pressure)]^0.5 X (area)
=[2 (4.825 kg / m^3)X (1,600,000 Pa]^0.5 X (0.1178 m^2)
= 462.87 kg / s
&nbp;
FIND MAXIMUM LIQUID WATER MASS INJECTION RATE INTO NaK FROM A SINGLE STEAM GENERATOR TUBE FAILURE:
Now find the maximum rate at which liquid H2O can enter the NaK on a single steam generator tube failure:
Recall that the cross sectional area for a single steam generator tube (1 / 2 inch diameter tube sheet hole )is:
1.2667 X 10^-4 m^2
Hence the maximum water jet flow rate into the NaK for a single tube failure is:
(mass flow rate) = [2 (density) X (differential pressure)]^0.5 X (area)
= [2 (1000 kg / m^3)(8,300,000 Pa)]^0.5 X 1.2667 X 10^-4 m^2
= [1.288 X 10^5 kg m^2-s] X 1.2667 X 10^-4 m^2
= 17.86 kg / s
MAXIMUM STEAM INJECTION RATE INTO NaK FROM A SINGLE STEAM GENERATOR TUBE FAILURE:
(mass flow rate) = [2 (density) X (differential pressure)]^0.5 X (area)
= [2 (28.384 kg / m^3) X (8,300,000 Pa)]^0.5 X 1.2667 X 10^-4 m^2
= 2.1706 kg / s
CONCLUSION:
17.86 kg / s X .20725 m^3 / kg
= 3.70 m^3 / s
We need to calculate the transient pressure rise related to this steam bubble accelerating NaK in the vent pipe.
This high pressure steam bubble that will push ahead of it the column of NaK in the vent pipe. The rate of NaK discharge into the vacuum above the NaK column in the vent pipe at the maximum tolerable NaK pressure of 1.7 MPa is given by:
(mass flow rate) = [2 (density) X (differential pressure)]^0.5 X (area)
or
(volume flow rate) =[2 (differential pressure) / (density)]^0.5 X (area)
= [2 (1,600,000 Pa)/ (866 kg / m^3)]^0.5 X (0.1178 m^2)
= 60.788 [(kg / m s^2) / (kg / m^3)]^0.5 X (0.1178 m^2)
= 7.161 m^3 / s
In essence this system design can easily accommodate the NaK pressure pulse accompanying sudden failure of a single tube in a steam generator.
The NaK discharge rate into the vacuum is more than sufficient to keep the peak pressure in the NaK under 1.7 MPa. This pressure pulse is potentially the result of a single steam generator tube failure that injects water into the NaK that flashes to steam forming a bubble that displaces NaK at the rate 3.7 m^3 / s.
This web page last updated June 6, 2025
Home | Energy Physics | Nuclear Power | Electricity | Climate Change | Lighting Control | Contacts | Links |
---|